SPECIFICATION DC SUPPLY CONTINUOUS VOLTAGE RATING 5 V to 35 V continuous CRANKING DROPOUTS Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries MAXIMUM OPERATING CURRENT 530 mA at 12 V, 280 mA at 24 V MAXIMUM STANDBY CURRENT 320 mA at 12 V, 160 mA at 24 V CHARGE FAIL/EXCITATION RANGE 0 V to 35 V OUTPUTS OUTPUT A (FUEL) 15 A DC at supply voltage OUTPUT B (START) 15 A DC at supply voltage OUTPUTS C & D 8 A AC at 250 V AC (Volt free) AUXILIARY OUTPUTS E to L 2 A DC at supply voltage GENERATOR & BUS Of DSE8620 MKII VOLTAGE RANGE 15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) FREQUENCY RANGE 3.5 Hz to 75 Hz MAGNETIC PICK-UP VOLTAGE RANGE +/- 0.5 V to 70 V FREQUENCY RANGE 10,000 Hz (max) BUILT-IN GOVERNOR CONTROL MINIMUM LOAD IMPEDANCE 500Ω Fully isolated GAIN VOLTAGE 0 V to 10 V DC Fully isolated OFFSET VOLTAGE 0 V to 10 V DC Fully isolated BUILT-IN AVR CONTROL MINIMUM LOAD IMPEDANCE 500Ω Fully isolated GAIN VOLTAGE 0 V to 10 V DC Fully isolated OFFSET VOLTAGE +/- 10 V DC Fully isolated For more products, check this: DSE8610-MKII Synchronization Controller If you want more related products, click here.