Diesel Unit Four Protection Module GTR17ASM17 Power Failure Self-Starting Generator Controller 220V: Gen Part Web is a global Online distributor of Automobile Accessories & Parts, Diesel and Gas Generator Sets. You can purchase Cheaper Electronic parts. Hot Selling and Fast Shipping.
![](https://static.wixstatic.com/media/569cf5_34fe939fa1f64b10a18e1fdb26ea0500~mv2.png/v1/fill/w_468,h_346,al_c,q_85,enc_auto/569cf5_34fe939fa1f64b10a18e1fdb26ea0500~mv2.png)
DIESEL UNIT FOUR PROTECTION MODULE GTR17ASM17 POWER FAILURE SELF-STARTING GENERATOR CONTROLLER 220V
The module GTR-17 is a low-cost Generator controller equipped with Auto Start/Stop functions, protections, alarm, annunciation, etc. Monitoring and protections include: Running, Over Speed, High Water Temperature, Low Oil Pressure, Over Crank, Emergency Stop, and Low Battery.
PANEL
1. LED
Emergency Shutdown
Low Battery Warning
Over Speed Shutdown
High Coolant Temp Shutdown
Low Oil Pressure Shutdown
Fail To Start
RunningPower
2. Key Switch
OFF: Stop running engine / Reset Alarm.
ATS: Auto Start function by detected ATS terminal l2.
MANUAL: Manual start engine
Protections and Parameters:
Auxiliary shutdown protection: 1 Sec, N.C
Low battery warning: 5sec,10.5 / 21 VDC
Over speed protection: 2sec, 55/66 Hz
High water temp. protection: 2 sec, N.O
Low oil press. Protection:2 sec, N.C/N.O
Over crank: 3 attempts
Cranking speed up limited: 0.5sec 16 Hz
Protection hold-off timer: 5 sec
SPECIFICATIONS OF DIESEL UNIT FOUR PROTECTION MODULE:
DC Supply: DC 8-36V
Power Consumption: MAX 5 W
Measuring Frequency:0-80 Hz(AC Volt: 25 V - 300 V
Relay Output:
Start Output: 2 A
Valve Output: 2 A
Idle/Pre-heat Output: 2 A
Alarm Output: 2 A
Stop Output: 2 A
Dimension(W*H*D):72mm*72mm*58mm
Panel Cut-Out(W*H):68mm*68mm
Ambient Temperature Range:-10°C - 85°C
Weight:200g
For more products, check this: BeK3 3phase AMF Controller